26 Important Product Information
GFK-1671P
Problems Resolved
Problems Resolved by Version 2.01
Print issues resolved:
ID Description
CR74863/
CR72266
Printout of long rungs results in undesirable output .
Details: If the length of a rung in Ladder Editor exceeds the page width, then the rung will be
printed across two pages.
Resolution: VersaPro 2.01 now has a ‘Fit to Page’ feature to fit the rung in the width of a
single page in the Ladder printouts. Check the ‘Fit Ladder Diagram Printout to Page’ option in
the Tools->Options menu Ladder Tab to turn on this option. Checking off this option will wrap
the rung to the next available line in the Ladder printout. Please note that this option is checked
on by default.
CR75849
Problem with printing LD Logic with Comments in Windows 2000.
Details: If you print an LD program with Comments in Windows 2000, the text after the
comments may print with a much larger font.
Resolution: The LD font should be set to Arial 8-pt and the print resolution to 300 dpi. To set
the LD font to Arial 8-pt:
1. Open the Options dialog box from the VersaPro Tools menu.
2. Click on the Display tab.
3. Select Category ‘LD’. Now Select Font ‘Arial’ and Size ‘10’ from the list.
Check the ‘Fit Ladder Diagram Printout to Page’ option in the Tools->Options menu Ladder
Tab.
15928
Problem with Hardware configuration report for VersaMax PLC
Details: If you print the HWC report for a VersaMax PLC with added carrier/bases past slot 1
the report will not show that information. Only the Slot 0 and Slot 1 information will be
included in the report.
Ethernet Global Data issues resolved:
ID Description
CR75993
%GA, %GB, %GC Data Types for Ethernet Global Data Not Allowed in VersaPro.
Details: VersaPro 2.00 has a limit has a limitation that prevents the use of %GA, %GB and
%GC as reference types for Ethernet Global Data exchanges.
Resolution: VersaPro 2.01 now has the option to use %GA to %GE as reference types for
Ethernet Global Data exchanges.
16457
VersaPro translates incorrect EGD when a 1.10 folder is imported to 1.5 or 2.0.
Details: When a 1.10 folder is imported into VersaPro 1.5 or 2.0, the EGD range data is not
imported correctly. The Offset entry is sorted to place Status in the first row instead of 0.0 but
the rest of the range data is not sorted accordingly.