Open Issues and Problems
ID Description
CR73532
VersaPro will not Import 90-30 Control Folder.
Details: VersaPro will not import a Control 2.30 Series 90-30 351 folder containing a block
with the following rung:
---|/|------|/|------| |-----------(S)-
| |
| +-------(S)-
|
+--| |------------(S)-
| |
| +-------(S)-
|
+---------------(R)--
When the import fails, VersaPro displays a dialog box stating “The import operation has failed
due to unsupported content. Please see the Information Window for more details.”
Resolution: Control is generating incorrect code for this rung and VersaPro flags the error
properly. You should avoid this type of construct for folders that must be imported from
Control to VersaPro.
CR73854
VersaPro cannot import Control folders configuration without Logic.
Details: VersaPro cannot import Control folders with empty logic. You will get the following
error:
Error: Failure reading
C:\CIMPLICITY\Control\folders\test2.dir_f3x\test2\test2\test2\_MAIN.pdt.
Error: Unable to import the logic file.
Resolution: When importing Control folders into VersaPro, add at least one rung of logic to
ensure that the folder will import correctly.
CR73855
Control hardware configuration seems to not import properly if hardware configuration
binary is not updated.
Details: Create a simple folder with Control with two APMs and a DSM302. Then import
with VersaPro and a DEFAULT hardware configuration was created.
Resolution: The user must be in Control hardware configuration screen and invoke the update
binary selection and save the folder before trying to import the Control folder into VersaPro.