38 Important Product Information
GFK-1671P
Open Issues and Problems
ID Description
CR74424
Loading autoconfigured VersaMax modules results in similar but wrong module.
Details The following list of modules have the same board IDs and VersaPro is unable to
distinguish between them when loading an autoconfigured module.
IC200MDL650 loads as IC200MDL636
IC200MDL750 loads as IC200MDL742
IC200MDL331 loads as IC200MDL329
IC200MDD844 loads as IC200MDD842
IC200MDL141 loads as IC200MDL140
Resolution: After loading the listed autoconfigured VersaMax modules, you should change
the configuration to the proper module in VersaPro and then store the configuration to
VersaMax. After storing the configuration, you will be able to load the configuration properly.
CR74772
“Adapter Name is Not Allowed to be blank” message during EGD Restore.
Details: Create two folders with EGD exchanges: Folder 1 and Folder 2
Folder 2 contains Exchanges to be imported.
1. Open Folder 1.
2. Restore EGD from Folder 2
3. “Adapter Name is Not Allowed to be blank” message is encountered when EGD and Name
Resolution are being restored. The message continues to be displayed 13 times with each
OK click.
Resolution: Delete the adapter name in the Ethernet configuration for folder 1.